• CLSA-6

Product Description

Combination of coarse and fine protection of data and M&C lines. For LSA separating strips.

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

6V AC

Maximum operating voltage 

Uc

9V AC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

400V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

13V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

1,50MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

-70 °C

ETIM Class 

 

EC001625

Mounting 

 

LSA disconnection rail

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

 

 

 

 

 

Write a review

Please login or register to review

CLSA-6


Related Products

CLSA-ISDN

CLSA-ISDN

Product DescriptionCombination of coarse and fine protection of telecommunication equipment including ADSL. For protection of M&C and data lines a..

Send Price Request

DL-Cat. 5e

DL-Cat. 5e

Product DescriptionFine protection for one port of Ethernet Cat. 5e. installation at the boundary of LPZ 2 and LPZ 3 zones directly in front of the de..

Send Price Request

 Spare Module For All SLP-275 Line - 8595090523680

 Spare Module For All SLP-275 Line - 8595090523680

Technical specificationclass ETIM : EC000941..

Send Price Request

DL-Cat.6 -60V

DL-Cat.6 -60V

Product DescriptionFine protection for one port of Ethernet Cat. 6. Installation at the boundary of LPZ 2 and LPZ 3 zones directly in front of the dev..

Send Price Request