• CLSA-48

Combination of coarse and fine protection of data and M&C lines. For LSA separating strips.

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

36V AC

Maximum operating voltage 

Uc

51V DC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

400V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

65V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

6,50MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

70 °C

Mounting 

 

LSA disconnection rail

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC001625

 

 

 


Write a review

Please login or register to review

CLSA-48


Related Products

DP-060-V/1-16

DP-060-V/1-16

Protection of power supply with output from the midle and non-grounded pole. Installation as close as possible to the protected equipment.Technical sp..

Send Price Request

CLSA-12

CLSA-12

Combination of coarse and fine protection of data and M&C lines. For LSA separating strips.Technical specifications Type of SPD ..

Send Price Request

ZX-3, N50 F/M

ZX-3, N50 F/M

ZX-3, N50 F/MN50 connectors, quarter-wave short circuit.Protection of coaxial lines and telecommunication equipment. Installation at the boundary of L..

Send Price Request

DL-ISDN SV

DL-ISDN SV

Efficient protection for ISDNCombination of coarse and fine protection of one pair of ISDN line of telecommunication equipment. Installation at the bo..

Send Price Request