RE – Y(St)YSWAY – PIMF/TIMF, RE – 2Y(St)YSWAY – PIMF/TIMF, RE – 2X(St)YSWAY – PIMF/TIMF

RE-Y(St)YSWAY-PiMF/TiMF             (CU/PVC/PSCR(TSCR)/OSCR/PVC/SWA/PVC)
RE-2Y(St)YSWAY-PiMF/TiMF           (CU/PE/PSCR(TSCR)/OSCR/PVC/SWA/PVC)
RE-2X(St)YSWAY-PiMF/TiMF           (CU/XLPE/PSCR(TSCR)/OSCR/PVC/SWA/PVC)

       

Technical and Electrical Properties (20°C)
Cross Section (mm²) 0.50 0.75 1.00 1.30 1.50 2.50
Conductor (Cu) (stranded) 7x0.30 mm 7x0.37 mm 7x0.43 mm 7x0.49 mm 7x0.52 mm 7x0.67 mm
Insulation Thickness (nom.mm) 0.40 0.40 0.40 0.50 0.50 0.60
Conductor Resistance (max. Ω/km) 36 24.5 18.1 14.2 12.1 7.41
L/R Ratio (max) 25uH/ Ω 25uH/ Ω 25uH/ Ω 40uH/ Ω 40uH/ Ω 60uH/ Ω
             
Operating Voltage 300V / 500 V          
Test Voltage Core/Core 2000 V Core/Screen 1000 V    
Capacitance (800 Hz) max.nF/km PVC lnsulation:220 PE lnsulation:115   XLPE lnsulation:115     Capacitance values may increase by  20% up to 4 pairs 
Capacitance Unbalanced (max.) 500pF / 500m          
Insulation Resistant (min. M.Ωxkm) PVC:100 PE: 5000 XLPE: 5000      
Temperature Range PVC and PE fixed -30°C ..... + 70°C. during installation -5°C ...... +50°C
  XLPE fixed -30°C ..... + 90°C. during installation -5°C ...... +50°C
Min. Bending Radius (fixed] 10 x Cable diameter        
Oxygen Index Min.29%          
Flame Tests IEC 60332-1, IEC 60332-3-22 (CAT-A), (BS 4066 part 1&3), EN 50266-2-2
Oil Resistance (IEC 60811) ASTM No 2 oil 70°C 4 hours
             
             

For the Yw and LSF (heat resistant PVC and low smoke fume) versions please contact our sales dept.

PART NUMBER NO OF CORES/CROSS SECTION (mm² ) CABLE DIAMETER (mm) COPPER WEIGHT (Kg/Km) CABLE WEIGHT (Kg/Km)

1.30mm²

 
50Y61302-X 2x2x1.30 15.20 65 460
50Y61304-X 4x2x1.30 19.40 120 655
50Y61308-X 8x2x1.30 24.70 230 1,101
50Y61310-X 10x2x1.30 28.80 288 1,570
50Y61312-X 12x2x1.30 30.30 340 1,705
50Y61316-X 16x2x1.30 33.80 455 2,010
50Y61320-X 20x2x1.30 35.80 570 2,520
50Y61324-X 24x2x1.30 38.70 680 2,920
         

1.50mm²

 
50Y61502-X 2x2x1.50 16.00 72 470
50Y61504-X 4x2x1.50 20.50 135 810
50Y61508-X 8x2x1.50 25.00 258 1,150
50Y61510-X 10x2x1.50 29.00 318 1,620
50Y61512-X 12x2x1.50 30.00 380 1,770
50Y61516-X 16x2x1.50 33.50 502 2,118
50Y61520-X 20x2x1.50 36.50 625 2,680
50Y61524-X 24x2x1.50 40.20 750 3,082

Y: Insulation Type (0:PVC, 2:PE, 4:XLPE)

• Please contact our sales dept.for the 2.50 mm² cross section, STA armoured and triple versions.
• Black PE sheathed or PE inner sheathed type also available.

The cable weight can be slightly higher in PVC insulated version.
X: Sheath Colors (0:Blue, 1 :Black, 2:Gray)

PART NUMBER NO OF CORES/CROSS SECTION (mm² ) CABLE DIAMETER (mm) COPPER WEIGHT (Kg/Km) CABLE WEIGHT (Kg/Km)
0.50mm²    
50Y60502-X 2x2x0.50 12.20 35 315
50Y60504-X 4x2x0.50 14.80 58 430
50Y60508-X 8x2x0.50 18.00 105 602
50Y60510-X 10x2x0.50 21.00 130 811
50Y60512-X 12x2x0.50 22.00 153 904
50Y60516-X 16x2x0.50 24.20 202 1,010
50Y60520-X 20x2x0.50 28.00 252 1,401
50Y60524-X 24x2x0.50 30.50 302 1,690
         

0.75mm²

 
50Y60802-X 2x2x0.75 13.50 45 345
50Y60804-X 4x2x0.75 17.00 77 490
50Y60808-X 8x2x0.75 19.50 150 795
50Y60810-X 10x2x0.75 22.50 180 960
50Y60812-X 12x2x0.75 24.00 215 1,080
50Y60816-X 16x2x0.75 27.50 280 1,520
50Y60820-X 20x2x0.75 29.50 350 1,750
50Y60824-X 24x2x0.75 32.00 419 2,250

1.00mm²

 
50Y61002-X 2x2x1.00 13.80 54 385
50Y61004-X 4x2x1.00 17.00 96 540
50Y61008-X 8x2x1.00 21.00 185 902
50Y61010-X 10x2x1.00 24.20 225 1,110
50Y61012-X 12x2x1.00 25.80 272 1,352
50Y61016-X 16x2x1.00 29.80 360 1,701
50Y61020-X 20x2x1.00 31.00 450 1,880
50Y61024-X 24x2x1.00 35.80 538 2,480
         
Download PDF

 
               ABU DHABI                  DUBAI                       JAFZA                                                 MUSCAT                                                   DOHA

UAE +971 2 5557351    +971 4 3352995    +971 4 8831401        OMAN  +968 24 750205        QATAR   +974 44150543

       

       

       

Construction  
Conductor Plain annealed stranded copper wires (IEC 228, HD 383, BS 6360, VDE 0295 Class 2)
Insulation PVC (EN 50290-2/ VDE 0207 YI1), PE (VDE 0207 2YI1) or XLPE
Core Colors Pair Black/White, numbered
  Triple Black/White/Red, numbered
Individual Separator Polyester tape
Individual Shielding AL-PES tape (with 0.60 mm tinned copper drain wire)
Communication Core 0.50 mm² XLPE insulated, orange (for more than one pair or triple cables)
Lay-up Shielded Pairs/Triples in layers are stranded together with the communication core
Separator Polyester tape
Overall Shielding AL-PES tape (with 7x0.30 mm tinned copper drain wire)
Inner Sheath PVC, Black (VDE0207 YM1/HD21.1.S4TM1)
Armour Round galvanized steel wire (Min. Diameter 0.90 mm)
Sheath UV resistant, flame retardant PVC (EN 50290-2/ VDE 0207 YM1/HD 21.1.S4 TM1), Black or Blue (RAL5015) (other colors upon request)
Reference Standards BS 5308 part1, part2; EN 50288-7; VDE 0815