• Module of surge protection , 10 A, installation C High

Fault signalling by supply interruption.

  • Surge arrester especially for LED lights.
  • Installation close to protected equipme in LV power circuits.
  • Also for equipment in external part of building with high exposure level (according to IEEE C62.41.2).


Specifications:

ameter name

Parameter value

Type of SPD

T2,T3

Nominal voltage

Un

230 V AC

Maximum operating voltage

Uc

320.00 V AC

Nominal load current

IL

10.000 A

Type of network

TN|TT

Maximum overcurrent protection

32 A gL/gG or C 32 A

Short-circuit current rating

ISCCR

3.0 kA

Residual current

IPE

0.004 mA

Nominal discharge current (8/20 µs) L-N

In

5.00 kA

Nominal discharge current (8/20 µs) N-PE

In

5.00 kA

Maximum discharge current (8/20 µs) L-N

Imax

10.00 kA

Maximum discharge current (8/20 µs) N-PE

Imax

10.00 kA

Test voltage L-N

Uoc

10.0 kV

Test voltage L-PE

Uoc

10.0 kV

Test voltage N-PE

Uoc

10.0 kV

Voltage protection level mode L-N

Up

1.30 kV

Voltage protection level mode L-PE

Up

1.50 kV

Voltage protection level mode N-PE

Up

1.50 kV

Response time L-N

ta

25 ns

Response time N-PE

ta

100 ns

TOV 5 s L-N

335 V

TOV 5 s L-PE

440 V

TOV characteristic (TOV 5 s)

withstand

TOV 120 min L-N

440 V

TOV characteristic (120 min)

withstand

TOV 200 ms L-PE

1 455 V

TOV 200 ms N-PE

1 200 V

TOV characteristic (TOV 200 ms)

safe failure

Cross-section of connected conductors solid (max)

2.50 mm2

Cross-section of connected conductors stranded (max)

1.50 mm2

Fault indication

loss of voltage, dark grey indication field

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC000942

Customs tariff number

85363030

EAN

8595090560449


Dimensions:






Write a review

Note: HTML is not translated!
Captcha

Module of surge protection , 10 A, installation C High

0 reviews / Write a review

* Required fields



Related Product

AC diverter ,for suppression of AC voltage

AC diverter ,for suppression of AC voltage

SPD for Cathodic Corrosion Protection System.Combines an AC current diverter and a SPD in one enclos..

Digital tester for status monitor of SPDs

Digital tester for status monitor of SPDs

Measurement of insulation resistance. It can be used to provide a more accurate imagine of the SPD s..

Automatic VLD class 2 tester