Protection of power supply with output from the midle and non-grounded pole, also for powwer suply with
one pole grounded. Installation as close as possible to the protected equipment.
Technical specifications
Type of SPD |
|
T3,
C2 |
Connection (input - output) |
|
terminals-terminals |
Location of SPD |
|
ST
2 |
Nominal voltage |
Un |
60V AC |
Maximum operating voltage |
Uc |
75V AC and 75V DC |
Nominal load current |
IL |
16,000A |
C2 nominal discharge current (8/20 µs) per
core |
In |
2,00kA |
C2 voltage protection level mode core-core at In |
Up |
390V |
C2 voltage protection level mode core-PE at
In |
Up |
750,00V |
Test voltage L+ - L- |
|
4,0kV |
Test voltage L+(L-)-PE |
|
4,0kV |
Test voltage M-PE |
|
4,0kV |
voltage protection level L+ - L- |
|
0,39
kV |
voltage protection level L+(L-)-PE |
|
0,75
kV |
voltage protection level
M-PE |
|
0,75
kV |
Maximum overcurrent protection |
|
16
A gL/gG or B 16 A |
Response time L+ - L- |
|
25ns |
Response time L+(L-)-PE |
|
100ns |
Response time M-PE |
|
100ns |
Cross-section of connected conductors solid
(min) |
|
0,14mm2 |
Cross-section of connected conductors solid
(max) |
|
4,00 mm2 |
Cross-section of connected conductors
stranded (min) |
|
0,14 mm2 |
Cross-section of connected conductors stranded (max) |
|
2,50 mm2 |
Fault indication |
|
red indicator |
Degree of protection |
|
IP
20 |
Range of operating temperatures - min |
|
-40 °C |
Range of operating temperatures - max |
|
-70 °C |
Mounting |
|
DIN rail 35 mm |
According to standard |
|
EN
61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012, EN 61643-11:2012, IEC
61643-11:2011 |
DP-060-V/1-F16
- Brand: SALTEK - Czech Republic
- Categories: Surge Protection Devices MPN: 8595090556671
- Product Code: DP-060-V/1-F16
Related Products
TNS Protection - 8595090517221
SPD type 2 – surge arrester 4-pole arrester for 3-phase TNS networks 4-pole varistor surge protection to be installed in low-voltage distributions ..
HX-090 N50 F/M
N50 connectorsProtection of coaxial lines and telecommunication equipment. Installation at the boundary of LPZ 0 and LPZ 1 zones at the line inpu..
CLSA-HF6
Combination of coarse and fine protection designed to protect data lines with high speed ratesTechnical specifications Type of SPD ..
CLSA-12
Combination of coarse and fine protection of data and M&C lines. For LSA separating strips.Technical specifications Type of SPD ..